FlowCon SM DN15-250 (1/2”-10”) 09/2025 Service Display 16 * current 0.0 mA 17 * batt 4.3 Vdc 18 * batt 20.0ma 19 * batt 4 20 * overrid 0pc 21 * speed 100pc 22 * version FL1 23 * s/n 240- 24 * reset no 25 * factory no Description Current mA used by the motor *scrolling top: motor current Current V of battery *scrolling top: batt voltage Current mA of battery *scrolling top: batt current Number of charges done by the bat- tery. *scrolling top: batt charge count Electrical override *scrolling top: input overrid Actuator rotation speed *scrolling top: speed adjust Actuator firmware version *scrolling top: version Actuator serial number *scrolling top: s/n Reset alarms (which do not automatically reset) *scrolling top: err 02 was over torque err 07 valve Factory reset *scrolling top: factory reset Values Unit is mA Unit is VDC Only valid for SM.0.0.1.4/6 models Unit is mA Only valid for SM.0.0.1.4/6 models Only valid for SM.0.0.1.4/6 models Default: 0% Options: 0%-100% Automatically disables after 15 minutes or when actuator is restarted or factory reset Default: 100% Options: 0%-100% S/N is for identification and traceability Default: NO Options: NO or YES Reset of ERR 07 forces a re-calibration of the valve All values will be set to default and a soft reset is generated. Default: NO Options: NO or YES This paper is a supplement to the FlowCon SM Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 3 of 6