FlowCon SM DN15-250 (1/2”-10”) 09/2025 Service Display 06 * control 0.0 vdc 07 * feedbac 2.0 vdc 08 * power 23.7DC 09 * fail 1 min 10 * digital close 11 * maximum 35.0°C 12 * count 2 13 * minimum -2.0°C 14 * count 2 15 * torque 0.0 Description Current input signal to actuator Values Only valid if programming menu 5 is set to VDC or mA. Otherwise skipped *scrolling top: control signal Current feedback signal from actuator Only valid if programming menu 5 is set to VDC or mA. Otherwise skipped *scrolling top: feedbac Current power supplied to actuator Unit is VDC or VAC *scrolling top: power supply Wait time from power failure to failsafe mode activation *scrolling top: fail safe wait time Current digital signal to actuator *scrolling top: digital input Max temperature, which the actuator has experienced. Temperature sensor holds ±0.5°C accuracy *scrolling top: maximum temp Number of periods (of 5 minutes each) that the actuator has experienced max temperature. Temperature sensor holds ±0.5°C accuracy *scrolling top: maximum temp count Min temperature, which the actuator has experienced. Temperature sensor holds ±0.5°C accuracy *scrolling top: minimum temp Number of periods (of 5 minutes each) that the actuator has experienced min temperature. Temperature sensor holds ±0.5°C accuracy *scrolling top: minimum temp count Current torque value Default: 1 Options: 1 or 15. Unit is minutes Only valid for SM.0.0.1.4/6 models Values: Open, Stop or Close Only valid if programming menu 5 is set to digital 2-position or 3-point floating. Otherwise skipped Unit is °C Unit is °C Unit is Nm Calculated from mA in motor *scrolling top: TORQUE This paper is a supplement to the FlowCon SM Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 2 of 6
下载PDF文件