FlowCon FT Actuators FlowCon Thermal Actuators, NC SPECIFICATIONS FlowCon FT.0.2 Supply voltage: Type: Power consumption: Control signal: Failsafe function: Operation time: Actuating force: Ambient temperature: Protection: Cable: FlowCon FT.0.3 Supply voltage: Type: Power consumption: Control signal: Failsafe function: Operation time: Actuating force: Ambient temperature: Protection: Cable: 24V AC -10%.+20%, 50/60 Hz Thermal 1.2W Analog 0-10V Yes, normally closed 1 Approximately 4.5 minutes 2 125N ±5% 0°C to +60°C / +32°F to +140°F IP54 including upside-down, class III Plug-in, 3 wires x 0.22 mm 2 , 1 m Plug-in, 3 wires x AWG24, 3.3 ft 230V AC ±10%, 50/60 Hz Thermal 1.2W ON/OFF Yes, normally closed 1 Approximately 4.5 minutes 2 125N ±5% 0°C to +60°C / +32°F to +140°F IP54 including upside-down, class II Fixed, 2 wires x 0.75 mm 2 , 1 m Fixed, 2 wires x AWG18, 3.3 ft Note 1: To ensure that the valve is in an open position during commissioning of the system, the actuator will be delivered in open position and remain in this position until it is electrically operated first time. Note 2: Closing time is approximately the double dependent on ambient temperature. Tech note · january 2023 · www.flowcon.com Page 1 of 3
Download PDF file