FlowCon SH DN50-250 (2”-10”) 04/2024 Flow rate settings, FlowCon SH6 Flow rate Valve size: DN200 and DN250 · 8” and 10” 35-600 kPaD · 5.1-87 psid SH.6.2 l/sec l/hr GPM Setting l/sec l/hr GPM Setting 9.21 33100 146 1.0 57.5 207000 911 6.0 9.69 34900 154 1.1 58.3 210000 924 6.1 10.2 36800 162 1.2 59.1 213000 936 6.2 10.8 38900 171 1.3 59.8 215000 948 6.3 11.5 41200 182 1.4 60.6 218000 960 6.4 12.1 43700 192 1.5 61.3 221000 972 6.5 12.9 46300 204 1.6 62.0 223000 983 6.6 13.6 49100 216 1.7 62.7 226000 994 6.7 14.5 52000 229 1.8 63.4 228000 1000 6.8 15.3 55100 242 1.9 64.0 230000 1010 6.9 16.2 58200 256 2.0 64.6 233000 1020 7.0 17.1 61500 271 2.1 65.2 235000 1030 7.1 18.0 64900 286 2.2 65.8 237000 1040 7.2 19.0 68400 301 2.3 66.4 239000 1050 7.3 20.0 71900 317 2.4 66.9 241000 1060 7.4 21.0 75600 333 2.5 67.4 243000 1070 7.5 22.0 79300 349 2.6 68.0 245000 1080 7.6 23.1 83100 366 2.7 68.4 246000 1080 7.7 24.1 86900 383 2.8 68.9 248000 1090 7.8 25.2 90800 400 2.9 69.4 250000 1100 7.9 26.3 94700 417 3.0 69.8 251000 1110 8.0 27.4 98700 435 3.1 70.2 253000 1110 8.1 28.5 103000 452 3.2 70.6 254000 1120 8.2 29.6 107000 470 3.3 71.0 256000 1130 8.3 30.8 111000 488 3.4 71.4 257000 1130 8.4 31.9 115000 506 3.5 71.8 258000 1140 8.5 33.0 119000 523 3.6 72.1 260000 1140 8.6 34.2 123000 541 3.7 72.5 261000 1150 8.7 35.3 127000 559 3.8 72.8 262000 1150 8.8 36.4 131000 577 3.9 73.2 263000 1160 8.9 37.5 135000 595 4.0 73.5 265000 1170 9.0 38.6 139000 613 4.1 73.8 266000 1170 9.1 39.8 143000 630 4.2 74.2 267000 1180 9.2 40.9 147000 648 4.3 74.5 268000 1180 9.3 41.9 151000 665 4.4 74.8 269000 1190 9.4 43.0 155000 682 4.5 75.1 270000 1190 9.5 44.1 159000 699 4.6 75.5 272000 1200 9.6 45.2 163000 716 4.7 75.8 273000 1200 9.7 46.2 166000 732 4.8 76.1 274000 1210 9.8 47.2 170000 749 4.9 76.5 275000 1210 9.9 48.3 174000 765 5.0 76.8 277000 1220 10.0 49.3 177000 781 5.1 50.2 181000 796 5.2 51.2 184000 812 5.3 52.2 188000 827 5.4 53.1 191000 842 5.5 54.0 194000 856 5.6 54.9 198000 870 5.7 55.8 201000 884 5.8 56.6 204000 898 5.9 57.5 207000 911 6.0 Accuracy: Greatest of either ±5 % of controlled flow rate or ±2% of maximum flow rate. Use the special designed key (FlowCon part no. ACC0001) for micrometer setting. A micrometer setting at 2.4 as illustrated above corresponds to a flow rate of: 20 l/sec - (type SH.6.2, range 35-600 kPaD) This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 5 of 6
Download PDF file