FlowCon SH DN50-250 (2”-10”) 04/2024 Flow rate settings, FlowCon SH5 Flow rate Valve size: DN125 and DN150 · 5” and 6” 30-600 kPaD · 4.5-87 psid 35-600 kPaD · 5.1-87 psid Setting SH.5.1 SH.5.2 l/sec l/hr GPM l/sec l/hr GPM 6.48 23300 103 7.10 25600 113 1.0 7.24 26100 115 8.06 29000 128 1.1 7.98 28700 127 8.98 32300 142 1.2 8.69 31300 138 9.87 35500 157 1.3 9.39 33800 149 10.7 38600 170 1.4 10.1 36200 160 11.6 41600 183 1.5 10.7 38600 170 12.4 44500 196 1.6 11.4 40900 180 13.1 47300 208 1.7 12.0 43100 190 13.9 50000 220 1.8 12.6 45200 199 14.6 52600 232 1.9 13.1 47300 208 15.3 55100 243 2.0 13.7 49300 217 16.0 57500 253 2.1 14.2 51200 226 16.6 59800 264 2.2 14.7 53100 234 17.2 62100 274 2.3 15.3 54900 242 17.8 64200 283 2.4 15.7 56600 250 18.4 66300 292 2.5 16.2 58300 257 19.0 68300 301 2.6 16.6 59900 264 19.5 70200 309 2.7 17.1 61500 271 20.0 72100 317 2.8 17.5 63000 227 20.5 73800 325 2.9 17.9 64400 284 21.0 75500 333 3.0 18.3 65800 290 21.4 77200 340 3.1 18.6 67100 295 21.9 78700 347 3.2 19.0 68300 301 22.3 80200 353 3.3 19.3 69500 306 22.7 81700 360 3.4 19.6 70700 311 23.1 83100 366 3.5 19.9 71700 316 23.4 84400 372 3.6 20.2 72800 321 23.8 85700 377 3.7 20.5 73800 325 24.1 86900 383 3.8 20.7 74700 329 24.5 88100 388 3.9 21.0 75600 333 24.8 89200 393 4.0 21.2 76400 337 25.1 90300 398 4.1 21.4 77200 340 25.4 91400 403 4.2 21.6 77900 343 25.7 92400 407 4.3 21.8 78600 346 25.9 93400 411 4.4 22.0 79200 349 26.2 94300 415 4.5 22.2 79800 352 26.5 95200 420 4.6 22.3 80300 354 26.7 96100 423 4.7 22.5 80800 356 26.9 97000 427 4.8 22.6 81300 358 27.2 97800 431 4.9 22.7 81700 360 27.4 98600 435 5.0 22.8 82100 362 27.6 99400 438 5.1 22.9 82400 363 27.8 100000 442 5.2 23.0 82700 364 28.1 101000 445 5.3 23.0 83000 366 28.3 102000 448 5.4 23.1 83200 367 28.5 102000 452 5.5 23.2 83400 367 28.7 103000 455 5.6 23.2 83500 368 28.9 104000 458 5.7 23.2 83600 368 29.1 105000 461 5.8 23.3 83700 369 29.3 105000 465 5.9 23.3 83800 369 29.5 106000 468 6.0 Accuracy: Greatest of either ±5 % of controlled flow rate or ±2% of maximum flow rate. Use the special designed key (FlowCon part no. ACC0001) for micrometer setting. A micrometer setting at 2.4 as illustrated above corresponds to a flow rate of: 15.3 l/sec - (type 1, range 30-600 kPaD) 17.8 l/sec - (type 2, range 35-600 kPaD) This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 4 of 6
Download PDF file