FlowCon SM DN15-250 (1/2”-10”) 02/2024 Programming Menu The programming menu is always accessible. To enter the program- ming menu, simultaneously press and for 6 seconds, until bottom line in display blinks. To change a value, press or . For quick scroll through values hold down or . Press to accept a value and go to next step and press to go to previous step. For fast menu exit press and simultaneously for 6 seconds. The actuator will automatically return to normal operation mode if no ac- tion is detected on arrow keys for 1 minute. All values selected in the programming menu are stored in non-volatile memory. Step Display 0 * Description Password. *scrolling top: ENTER PASS WORD Values Disabled by default Password: 3569266. Only if Enabled (in step 11). Change one digit at a time, press and to move between digits. At last digit, press to go to next step. 1 * Select language. *scrolling top: SELECT LANGUAG Default: English. Possibility to choose other languages later on (not currently an option). 2 * 3 * Select valve model onto which the actuator is installed. *scrolling top: SELECT VALVE MODEL Choose unit scale for flow rate. *scrolling top: SELECT UNIT SCALE Default: SM.0.0. Select from the 10 available valve models. Options: SM.1.1, SM.2.1. Default: l/sec. Options: l/sec or l/hr or GPM. 4 * 5 * Activate Flush mode at start-up. *scrolling top: SELECT FLUSH MODE Select type of control signal. *scrolling top: SELECT CONTROL SIGNAL Default: Enable. Options: Enable or Disable. When no control signal (analog) is detected at start up, flush mode is started (5/6 of fully opened). It will be dismissed when control signal is detected. Default: 2-10VDC. Options: 2-10VDC or 4-20mA or digital. Choose: • 2-10VDC for VDC • 4-20mA for mA • Digital for 2 position or 3 point floating. This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 4 of 8
Download PDF file