EM-239 PCB Single hall feedback 1 Voltmeter _ Act. 1 Act. 2 7 8 + Voltmeter Act. 1 Act. 2 1 7 8 EM-239 PCB _ + EM-239 PCB Check that the jumper is placed correctly (see Quick guide). Check the signal from the actuator by measuring the voltage on terminal 7 and 8. At lack of signal, run the actuator forwards and backwards to see the signal change from 12/24 V to 0 V. At lack of signal check cables and actuator. 12-24 V Dual hall feedback EM-239 PCB Voltmeter Voltmeter 1 2 _ + 1 _ Act. 1 Act. 2 Hall A Hall B Hall A Hall B 7 8 11 12 + Act. 1 Act. 2 EM-239 P Ha C ll B A Hall B Hall A Hall B 1 Voltmeter _ Motor outputs 7 8 11 12 + Voltmeter Act. 1 Act. 2 14 3 456 9 10 EM-239 PCB Frem FW Tilbage BW Check the feedback from the actuator when using dual hall. EM-239 PCB Check that the motor outputs are active. 14 9 10 Frem FW Tilbage BW Initialisation of the system EM-239 PCB 5 V Voltmeter 14 9 10 14 1 Frem Tilbage _ FW BW + EM-239 PCB The parallel system can be reset by activating terminal 9 and 10 (BACKWARDS and FORWARDS) at the same time. A reset can also be achieved by activating terminal 16. (HOME) 1 Ohmmeter 14 9 10 LINAKTHIRDPARTY.COM EM-239 PCB