Page number 6
SPECIFICATIONS Pressure sensors (P1 and P2) Supply voltage: Cable: Output: Media temperature: Pressure range 3 : Housing material: Protection: CE conformity: Connection: 12V DC No cable, but with quick-connector 4-20mA -10°C to +85°C / 14°F to +185°F 0-25 bar / 0-360 psi 304 stainless steel IP65 Yes 1/4” ISO Performance data: • Accuracy: • Stability: • Thermal effect on zero: • Thermal effect on span: • Electronic proof: • Response time: Note 3: Calibrated at factory at 24V DC ±1.5% FS (Full Scale) (tolerances can be software compensated in the FlowCon Intelligent Interface) 0.5% FS (Full Scale) ±0.05% ±0.1% FS (Full Scale) ±0.05% FS (Full Scale) Short circuit protection <20 msec (20 sec mean value calculated in the FlowCon Intelligent Interface) Tech note · FlowCon FIT-G · november 2024 · www.flowcon.com Page 6 of 15
Page number 7
DIMENSIONS AND WEIGHT Model no. Valve size PICV Valve FN.0.2 Actuator L1 H1 H2 FITG.x.15.x.x.2 FITG.x.20.x.x.2 FITG.x.25K.x.x.2 FITG.2.25.x.x.2 FITG.2.32.x.x.2 FITG.3.40.x.x.2 FITG.3.50.x.x.2 mm (in) 15 (1/2) 20 (3/4) 25 (1) 25 (1) 32 (1 1/4) 40 (1 1/2) 50 (2) mm (in) 81 (3.19) 85 (3.35) 102 (4.02) 128 (5.04) 191 (7.50) mm (in) 31 (1.22) 47 (1.85) 100 (3.94) mm (in) 124 (4.88) 144 (5.67) - Note 4: Weight includes PICV valve (brass), PICV actuator non-failsafe, Intelligent Interface and sensor kit. FH Actuator H2 mm (in) - - 195 (7.67) Weight 4 kg (lb) 1.51 (3.33) 1.53 (3.37) 1.73 (3.81) 1.70 (3.75) 2.71 (5.97) 5.30 (11.7) 4.80 (10.6) H2 H1 L1 BMS FlowCon FIT-G.1 with FN actuator, Intelligent Interface and sensor kit H2 H1 L1 BMS FlowCon FIT-G.3 with FH actuator, Intelligent Interface and sensor kit Tech note · FlowCon FIT-G · november 2024 · www.flowcon.com Page 7 of 15