Blue Black Red FlowCon FT Actuators 1B95050 - 04/2021 Wiring FT.0.2 Actuator 0-10V DC modulating 0-10V DC Power 24V AC Ground/common FT.0.3 / FT.0.4 Actuator 2-position, Normally Closed Start-up Sequence During FIRST TIME POWERING operating voltage must be applied for at least 6 minutes. Ensure to have the FlowCon FT.0.2 mounted on the valve, when powering as it has auto- matic stroke detection. Blue Brown Figure 3 Close Open Power 24V AC/DC 230V AC Ground/common 24V versions must be powered by a safety isolating transformer (for AC variant) according to EN 61558-2-6 or class II FCC-quality proofed or a switching power supply (for DC variant) according to EN 61558-2-16. For FT.0.2 the power supply must have a maximum power output of 100VA. FlowCon International assumes no responsibility for mistakes, if any, in any printed material. This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 2 of 2