Page number 6
WIRING INSTRUCTION THERMAL MODULATING EV.0.2 Actuator FlowCon EV Blue Black Red Input signal 0-10V DC Power 24V AC Ground/common THERMAL ON/OFF EV.0.3 / EV.0.4 / EVP.0.3 Actuator Brown FlowCon EV / EVP Blue Blue Brown Close Open EV.1.3 / EV.1.4 Actuator Power 24V 230V AC/DC AC/DC Ground/common Black Grey Close Open Power 242V3A0CV/ADCC Ground/common ELECTRICAL MODULATING FNP.0.2 Actuator 0(2)-10V modulating FlowCon FNP Blue Brown Grey FN.0.2 Actuator 0(2)-10V modulating Input signal 0(2)-10V DC <0.5mA Power 24V AC/DC Ground/common FlowCon FN Blue Brown Grey Yellow Green Input signal 0(2)-10V DC <0.5mA Feedback signal 0(2)-10V DC Power 24V AC/DC Signal ground Ground/common White Black EV.0.5 Actuator Close Open Power 120V AC Ground/common Tech note · FlowCon Essentia · december 2024 · www.flowcon.com Page 6 of 10
Page number 7
WIRING INSTRUCTION ELECTRICAL 2-POSITION FN.0.4 Actuator 2-Position, Normally Closed FlowCon FN Blue Brown Grey Close Open Power 24V AC/DC Ground/common PLEASE NOTE: FN.0.4 has a reation time of 0.8 sec. This is the time from giving a 24V power signal until the actuator starts to move. This is particular important if using a pulse power signal. ELECTRICAL 3-POINT FLOATING FN.0.4 Actuator 3-Point Floating, Normally Closed FlowCon FN Blue Brown Grey Close Stop Open Power 24V AC/DC Ground/common DESCRIPTION The FlowCon Essentia is a self balancing dynamic flow control valve that is pressure independent. Each valve has an adjustable maximum flow rate setting maintaining a full stroke to enable accurate flow limitation and balancing to the coil or zone that the valve is controlling, even at partial load. The valve comes in four different housing types, i.e DN15, DN20, DN25 (1/2”, 3/4”, 1”) female/female and DN15 (3/4”) male/male. The female/female housings are standard with p/t plugs and male/male housing comes without the p/t plug option. For use in fan-coil units, VAV applications and cooling ceilings for activation of the heating or cooling. ACCESSORIES • Adjustment key: • Pressure/temperature plug: ACC0001 ACC0013 Tech note · FlowCon Essentia · december 2024 · www.flowcon.com Page 7 of 10