Page number 2

SPECIFICATIONS FlowCon FNR.0.2-EQ Supply voltage: Type: Power consumption: Inrush current: Control signal: Resolution: Feedback: Control mode: Failsafe function: Manual override: Position indicator: Operation time: Actuating force: Stroke: Ambient temperature: Media temperature: Humidity rating: Protection: CE conformity: Cable: Closing point adjustment: FlowCon FNR.0.3 Supply voltage: Type: Power consumption: Control signal: Feedback: Failsafe function: Manual override: Position indication: Operation time: Actuating force: Stroke: Ambient temperature: Media temperature: Humidity rating: Protection: CE confomity: Cable: Closing point adjustment: 24V AC/DC ±15%, 50/60 Hz Electrical, bi-directional step motor 24V AC: 1VA standby / 6VA operating / 6VA max. 24V DC: 0.5W standby / 4W operating / 4W max. 1.8A (peak) Analog 0-10V DC 1:100 No Equal % Fail in place Yes. 4 mm (~5/32”) Allen Key Yes 5.5 sec/mm 200N (-30N/+70N) 1-8.5 mm / 0.04-0.33 in (auto adjusting) 0°C to +50°C / +32°F to +122°F 0°C to +120°C / +32°F to +248°F 0.80% rH, no condensation IP54, class III, including upside-down, indoor use only EN 60730 Fixed, 3 wires x 0.22 mm 2 , 1.5 meter Fixed, 3 wires x AWG24, 4.9 ft During operation the actuator will self-adjust according to the closing point and stroke length of the valve. 110/230V AC ±10%, 50/60Hz Electrical, bi-direction step motor 1VA standby / 6VA operating / 8VA max. Digital (2-position / 3-point floating) No Fail in place Yes. 4 mm (~5/32”) Allen Key Yes 27.2 sec/mm 200N (-30N/+70N) 1-8.5 mm / 0.04-0.33 in (auto adjusting) 0°C to +50°C / +32°F to +122°F 0°C to +120°C / +32°F to +248°F 0.80% rH, no condensation IP54, class II, including upside-down, indoor use EN 60730 Fixed, 3 wires x 0.50mm 2 , 1.5 meter Fixed, 3 wires x AWG20, 4.9 ft During operation the actuator will self-adjust according to the closing points and stroke length only of the valve. Tech note · FlowCon FNR actuators · may 2022 · www.flowcon.com Page 2 of 3

Page number 3

DIMENSIONS AND WEIGHT (NOMINAL) Actuator FNR.0.X L mm (in) 93.0 (3.66) W mm (in) 50.0 (1.97) W H mm (in) 88 (3.46) L T M30x1.5 Weight kg (lb) 0.23 (0.51) H FlowCon FNR.0.X MODEL NUMBER SELECTION Actuator force: 0 = High Control signal: 2 = 24V modulating 3 = 110V/230V digital Control mode (only for modulating version): Leave blank = Linear EQ = Equal% FNR . 0 . . Example: FNR.0.2 = FlowCon FNR actuator 24V modulating, linear control mode. WIRING INSTRUCTION ANALOG FNR.0.2 / FNR.0.2-EQ Actuator 0-10V modulating White Black Red Input signal 0-10V DC Power 24V AC/DC Ground/common DIGITAL FNR.0.3 Actuator 2-Position FNR.0.3 Actuator 3-Point Floating White Black Red White Black Red Open Close Power 110/230V AC Ground/common Stop Open Close Power 110/230V AC Ground/common UPDATES For latest updates please see www.flowcon.com FlowCon International can accept no responsibility for possible errors in any printed material. All rights reserved. Tech note · FlowCon FNR actuators · may 2022 · www.flowcon.com Page 3 of 3

    ...