SPECIFICATIONS FlowCon Actuator 2 EV.0.3.R EV.0.4.R Supply voltage 230V AC ±10%, 50/60 Hz 24V AC/DC -10%/+20%, 50/60Hz Type Thermal Thermal Power consumption 1.0 watt 1.0 watt Control signal Failsafe function 3 ON/OFF Normally closed ON/OFF Normally closed End switch Operation time 4 No Approx. 4 min No Approx. 4 min Ambient temperature 0ºC to +60ºC / +32°F to +140°F 0ºC to +60ºC / +32°F to +140°F Protection IP54 including upside-down, class II IP54 including upside-down, class III Cable Weight 5 Fixed, 2 x 0.75 mm 2 , 1 m PVC 2 x AWG20, 3.3 ft PVC 0.11 kg / 0.24 lb Fixed, 2 x 0.75 mm 2 , 1 m PVC 2 x AWG20, 3.3 ft PVC 0.11 kg / 0.24 lb Note 2: Note 3: Note 4: Note 5: FlowCon warranty is voided using other actuators than supplied or recommended by FlowCon International. To ensure that the valve is in an open position during commission of the system, the actuator will be delivered in a normal open position and remain in this position until it is electrically operated first time. Closing time is approximately the double dependent on ambient temperature. Weight includes actuator, adaptor ring and 1 meter cable. WIRING INSTRUCTION FlowCon EV.0.3.R / EV.0.4.R EV.0.3.R / EV.0.4.R Actuator Blue Brown Close Open Power 24V 230V AC/DC AC/DC Ground/common FlowCon EV Valve adaptor, red Tech note · FlowCon T-JUST · may 2025 · www.flowcon.com Page 2 of 6