SPECIFICATIONS (continued) Type EV.0.3.R, EV.0.4.R Valve adaptor, red Thermal actuator: FlowCon EV.0.3.R 1 , FlowCon EV.0.4.R 1 Supply voltage: EV.0.3.R: 230V AC, ±10% EV.0.4.R: 24V AC/DC, -10/+20% Control signal: ON/OFF, normally closed 2 Power consumption: 1.0 Watt Operation time: Approx. 4 min 3 Ambient temperature: 0°C to +60°C Protection: EV.0.3.R: IP54 including upside-down, class II EV.0.4.R: IP54 including upside-down, class III Cable: Fixed cable, 1 m / 3 ft Weight: 0.108 kg / 0.24 lb Note 1: FlowCon warranty is voided using other actuators than supplied or recommended by FlowCon International ApS. Note 2: To ensure that the valve is in an open position during commission of the system, the actuator will be delivered in a normal open position and remain in this position until it is electrically operated first time. Note 3: Closing time is approximately the double dependent on ambient temperature. Tech note · FlowCon T-JUST · february 2024 · www.flowcon.com Page 2 of 6