Page number 4
WIRING INSTRUCTION SM.0.0.0.3/4/6 Actuator 0(2)-10V modulating Black Blue White Green Input signal 0(2)-10V DC Feedback signal 0(2)-10V DC Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 2-position, Normally Closed Black Red White SM.0.0.0.6 Actuator RS-485 Serial BACnet A+ B- Signal ground SM.0.0.0.3/4/6 Actuator 2-position, Normally Open Black Blue White Red Green Black Blue White Red Green Close Open Feedback signal Power 24V AC/DC Ground/common Open Close Feedback signal Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 3-point floating, Normally Closed SM.0.0.0.3/4/6 Actuator 3-point floating, Normally Open Black Blue White Red Green Black Blue White Red Green Stop Open Close Feedback signal Power 24V AC/DC Ground/common Stop Close Open Feedback signal Power 24V AC/DC Ground/common Note: If feedback signal is not required, leave green wire detached. DESCRIPTION The SM series is a range of self-balancing dynamic flow control valves that are pressure independent and 2-way and ready to accept digital or analog input signals. Each valve has an adjustable maximum flow rate setting to enable flow limitation to and balancing of the coil or zone which the valve is controlling. All SM actuators are microprocessor based with a self-calibrating feature. The SM actuator range includes standard incl. feedback, failsafe and BACnet. All SM actuators are programmable and with display. The SM actuators accept analog 0(2)10V DC or 0(4)-20mA as well as digital 3-point floating or 2-position input signals and work with control mode of linear flow or linear rotation. The smaller range of SM-valves are all designed for double union piping connection. They are available in two different valve body sizes with a range of end connections. All shall have snap connection for fast mounting of actuator. Tech note · FlowCon SM 15-40 mm / 1/2”-1 1/2” · march 2024 · www.flowcon.com Page 4 of 7
Page number 5
FLOW RATE TABLE Model no. Valve size mm inch Control range kPaD psid Lowest settable max flow l/sec l/hr GPM 15 1/2 SM.1.1 20 3/4 32-320 4.6-46 0.176 633 2.78 25 1 25 1 SM.2.1 32 1 1/4 40-320 5.8-46 0.513 1850 8.13 40 1 1/2 Accuracy: Greatest of either ±5% of controlled flow rate or ±2% of maximum flow rate. Turn down ratio lowest max flow 38:1 Highest settable max flow l/sec l/hr GPM Turn down ratio highest max flow 0.685 2470 10.9 2.34 8420 37.1 228:1 FLOW RATE SETTINGS 5 Maximum Flow Rate DN15-DN25 · 1/2”-1” DN25-DN40 · 1”-1 1/2” 32-320 kPaD · 4.6-46 psid 40-320 kPaD · 5.8-46 psid l/sec 0.176 0.195 0.214 0.233 0.251 0.268 0.285 0.301 0.317 0.332 0.347 0.362 0.376 0.390 0.403 0.416 0.428 0.440 0.452 0.463 0.474 0.485 0.495 0.505 0.515 0.524 0.533 0.542 0.550 0.559 0.567 0.574 0.582 0.589 0.596 0.603 0.609 0.616 0.622 0.628 0.634 0.639 0.645 0.650 0.655 0.661 0.667 0.671 0.676 0.680 0.685 SM.1.1 l/hr 633 702 770 838 902 964 1030 1080 1140 1200 1250 1300 1350 1400 1450 1500 1540 1580 1630 1670 1710 1750 1780 1820 1850 1890 1920 1950 1980 2010 2040 2070 2100 2120 2150 2170 2190 2220 2240 2260 2280 2300 2320 2340 2360 2380 2400 2420 2430 2450 2470 GPM 2.78 3.09 3.39 3.69 3.97 4.24 4.51 4.77 5.02 5.26 5.50 5.73 5.96 6.18 6.38 6.59 6.78 6.97 7.16 7.33 7.51 7.68 7.84 8.00 8.16 8.30 8.44 8.59 8.71 8.86 8.98 9.09 9.22 9.33 9.44 9.55 9.66 9.76 9.85 9.95 10.1 10.1 10.2 10.3 10.4 10.5 10.6 10.6 10.7 10.8 10.9 l/sec 0.513 0.573 0.632 0.690 0.746 0.802 0.856 0.909 0.961 1.01 1.06 1.11 1.16 1.20 1.25 1.29 1.34 1.38 1.42 1.46 1.50 1.54 1.58 1.61 1.65 1.69 1.72 1.75 1.79 1.82 1.85 1.88 1.91 1.94 1.97 1.99 2.02 2.05 2.07 2.10 2.12 2.15 2.17 2.19 2.22 2.24 2.26 2.28 2.30 2.32 2.34 SM.2.1 l/hr 1850 2060 2280 2480 2690 2890 3080 3270 3460 3640 3820 4000 4170 4330 4500 4660 4810 4970 5120 5260 5400 5540 5680 5810 5940 6070 6190 6310 6430 6550 6660 6770 6870 6980 7080 7180 7280 7370 7460 7550 7640 7730 7810 7890 7970 8050 8130 8200 8280 8350 8420 GPM 8.13 9.08 10.0 10.9 11.8 12.7 13.6 14.4 15.2 16.0 16.8 17.6 18.3 19.1 19.8 20.5 21.2 21.9 22.5 23.2 23.8 24.4 25.0 25.6 26.2 26.7 27.3 27.8 28.3 28.8 29.3 29.8 30.3 30.7 31.2 31.6 32.0 32.5 32.9 33.3 33.6 34.0 34.4 34.8 35.1 35.5 35.8 36.1 36.4 36.8 37.1 Accuracy: Greatest of either ±5% of controlled flow rate or ±2% of maximum flow rate. Note 5: Above indicates selectable maximum flow rates defining the flow through the valve at maximum control signal, normally 10V. Each valve includes up to 1000 positions between the selected max.flow and closed valve with control signal selected to 0-10V. Tech note · FlowCon SM 15-40 mm / 1/2”-1 1/2” · march 2024 · www.flowcon.com Page 5 of 7