Page number 2

SPECIFICATIONS FlowCon PICV actuator 2 : FlowCon SM.0.0.0.3 (standard) FlowCon SM.0.0.0.4 (standard failsafe) FlowCon SM.0.0.0.6 (BACnet failsafe) Supply voltage: Type: Power consumption: Control signal: Resolution: Feedback: Control mode: Failsafe function: Manuel override: Position indicator: Operation time: Ambient temperature: Humidity rating: Housing material: Protection: CE conformity: Programming: Cable: Calibration: Valve-actuator coupling: Protocol: Interface: Device profile: Baud rates support: Services (BIBBS) supported: Participants: 22-26V AC, 50/60 Hz or 22-26V DC Electrical, Bi-directional synchronous motor SM.0.0.0.3: 2.0VA standby / 5.0VA operating / 12VA max. SM.0.0.0.4/6: 3.5VA standby / 5.0VA operating / 12VA max. Analog 0(2)-10V DC or 0(4)-20mA and digital 3-point-floating or 2-position 1:1000 (0-10V analog) and 1:800 (2-10V analog) Linear signal Auto (equal to analog control signal), 0-10V DC, 2-10V DC or 4-20mA Linear flow, Equal percentage, Linear rotation or Linear signal SM.0.0.0.3: Fail in place SM.0.0.0.4/6: Optional open or close (set on actuator) Yes No SM.1-2: 190 sec (from closed to fully open valve) -10°C to +50°C / +14°F to +122°F 5.95% rH, no condensation UL94 V0-rated plastic IP54 including upside-down mounting EN 60730, class II Programming of all settings on interface with buttons and display or via BACnet Fixed, 5 wires x 0.80 mm 2 / AWG18, halogen free, 1 meter / 3 ft Additional for BACnet versions: Fixed, 3 wires x 0.80 mm 2 / AWG18 halogen free, 1 meter / 3 ft Automatic at startup Easy snap coupling BACnet MS/TP EIA-485 / RS-485 BACnet Application Specific Controller (B-ASC) type server 9600, 19200, 38400 and 76800 DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B and DM-DCC-B Up to 32 recommended, max. 127 participants Note 2: FlowCon warranty is voided using other actuators than supplied or recommended by FlowCon International. Tech note · FlowCon SM 15-40 mm / 1/2”-1 1/2” · march 2024 · www.flowcon.com Page 2 of 7

Page number 3

DIMENSIONS AND WEIGHT (NOMINAL) Model no. Valve size mm (in) 15 (1/2) L mm (in) H mm (in) H1 mm (in) End connections C 3 ISO Female mm (in) ISO Male mm (in) Sweat mm 22 (0.87) 24 (0.95) 20 SM.1.1 20 108 59 185 22 25 (3/4) (4.25) (2.32) (7.28) (0.87) (0.99) 20 25 (1) - 39 (1.54) 22 25 (1) 35 (1.38) 40 (1.57) 34 SM.2.1 32 (1 1/4) 149 (5.87) 63 (2.48) 235 (9.25) 33 (1.30) 40 (1.57) 34 40 (1 1/2) 33 (1.30) 42 (1.65) - Note 3: Add end connection length to body length. Note 4: Weight includes valve and actuators. Weight 4 kg (lb) 2.9 (6.4) 4.6 (10.1) C L MODEL NUMBER SELECTION Body size: 1 = DN15-25 / 1/2”-1” 2 = DN25-40 / 1”-1 1/2” SM . .1. . . . Δ P control range: 1 = standard P/t plug requirements: 0 = no (p/t) plugs B = pressure/temperature plugs P = taps plugged Type of actuator: 0 = no actuator 3 = display standard (SM.0.0.0.3) 4 = display and failsafe (SM.0.0.0.4) 6 = display, BACnet and failsafe (SM.0.0.0.6) Union end connections (inlet x outlet): 0.0 = no union ends Model and size Female threaded FlowCon SM.1.1 15-25 mm / 1/2”-1” E = 15 mm / 1/2” F = 20 mm / 3/4” FlowCon SM.2.1 25-40 mm / 1”-1 1/2” G = 25 mm / 1” P = 32 mm / 1 1/4” Q = 40 mm / 1 1/2” Male threaded H = 15 mm / 1/2” I = 20 mm / 3/4” J = 25 mm / 1” J = 25 mm / 1” S = 32 mm / 1 1/4” T = 40 mm / 1 1/2” Sweat K = 15 mm L = 18 mm M = 22 mm N = 28 mm W = 35 mm Connection standard: I = ISO N = NPT Example: SM.2.1.B.3.Q.Q.I = SM 25-40 mm (1”-1 1/2”) body with p/t plugs, standard display actuator and 40 mm (1 1/2”) ISO female threaded end connections. H1 H C . Tech note · FlowCon SM 15-40 mm / 1/2”-1 1/2” · march 2024 · www.flowcon.com Page 3 of 7

    ...