Page number 4

DIMENSIONS AND WEIGHT (NOMINAL) Actuator SM.0.0.0.3 SM.0.0.0.4 SM.0.0.0.6 L mm (in) 194 (7.64) L W mm (in) 102 (4.02) H H mm (in) 81 (3.19) W Weight kg (lb) 1.23 (2.71) 1.27 (2.80) 1.30 (2.87) FlowCon SM.0.0.0.3/4/6 FlowCon SM.0.0.0.3/4/6 MODEL NUMBER SELECTION Actuator type: 3 = Standard 4 = Standard and failsafe 6 = BACnet and failsafe Example: SM.0.0.0.4 = FlowCon SM standard actuator with failsafe. SM . 0 . 0 . 0 . Tech note · FlowCon SM actuators · august 2024-2 · www.flowcon.com Page 4 of 5

Page number 5

WIRING INSTRUCTION SM.0.0.0.3/4/6 Actuator 0(2)-10V modulating Black Blue White Green Input signal 0(2)-10V DC Feedback signal 0(2)-10V DC Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 2-position, Normally Closed Black Red White SM.0.0.0.6 Actuator RS-485 Serial BACnet A+ B- Signal ground SM.0.0.0.3/4/6 Actuator 2-position, Normally Open Black Blue White Red Green Black Blue White Red Green Close Open Feedback signal Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 3-point floating, Normally Closed Open Close Feedback signal Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 3-point floating, Normally Open Black Blue White Red Green Black Blue White Red Green Stop Open Close Feedback signal Power 24V AC/DC Ground/common Note: For all setups: if feedback signal is not required, leave green wire detached. For modulating setup, red wire is not used and may be cut. Stop Close Open Feedback signal Power 24V AC/DC Ground/common UPDATES For latest updates please see www.flowcon.com FlowCon International can accept no responsibility for possible errors in any printed material. All rights reserved. Tech note · FlowCon SM actuators · august 2024-2 · www.flowcon.com Page 5 of 5

    ...