FlowCon SM Actuators FlowCon Electrical Actuators SPECIFICATIONS FlowCon SM.0.0.0.3 (standard) Supply voltage: Type: Power consumption: Control signal: Resolution: Feedback: Control mode: Failsafe function: Manual override: Position indicator: Operation time: Ambient temperature: Humidity rating: Protection: CE conformity: Housing material: Programming: Cable: Calibration: Valve-actuator coupling: BACnet: 22-26V AC, 50/60 Hz or 22-26V DC Electrical, Bi-directional synchronous motor 2.0VA standby / 5.0VA operating / 12VA max Analog 0(2)-10V DC or 0(4)-20mA and digital 3-point-floating or 2-position 1:1000 (0-10V analog) and 1:800 (2-10V analog) Linear signal Auto (equal to analog control signal), 0-10V DC, 2-10V DC or 4-20mA Linear flow, Equal percentage, Linear rotation or Linear signal Fail in place Yes No SM.1-5: 190 sec (from closed to fully open valve) SM.6: 317 sec (from closed to fully open valve) -10°C to +50°C / +14°F to +122°F 5.95% rH, no condensation IP54 including upside-down mounting EN 60730, class II UL94 V0-rated plastic Programming of all settings on interface with buttons and display Fixed, 5 wires x 0.75 mm 2 , halogen free, 1 meter Fixed, 5 wires x AWG18, halogen free, 3 ft Automatic at startup Easy snap coupling No Tech note · august 2024-2 · www.flowcon.com Page 1 of 5