FlowCon SM Actuators FlowCon Electrical Actuators SPECIFICATIONS FlowCon SM.0.0.1.3 (standard) Supply voltage: Type: Power consumption: Control signal: Resolution: Feedback: Control mode: Supply voltage failsafe: Control signal failsafe: Manual override: Position indicator: Operation time: • FlowCon valve SM.1-5: • FlowCon valve SM.6: Actuating force: Stroke: • FlowCon valve SM.1-5: • FlowCon valve SM.6: Ambient temperature: Humidity rating: Protection: CE conformity: 24V AC ±20%, 50/60 Hz or 24V DC ±20% Electrical, Bi-directional synchronous motor 24V AC: 2.2VA standby / 3.8VA operating / 15VA max 24V DC: 1.0W standby / 1.7W operating / 8.0W max Analog 0(2)-10V DC or 0(4)-20mA and digital 3-point-floating or 2-position 1:1000 (0-10V analog) and 1:800 (2-10V analog) Linear flow Auto (equal to analog control signal), 0-10V DC, 2-10V DC or 4-20mA Linear flow, equal percentage or linear rotation Fail in place Fail in place or settable 0-100% open Yes No 190 sec (from closed to fully open valve) 317 sec (from closed to fully open valve) 9 Nm opening / 7.5 Nm closing 2160° 3600° -10°C to +50°C / +14°F to +122°F 5.95% rH, no condensation IP54 including upside-down mounting EN 60730, class II Tech note · november 2025 · www.flowcon.com Page 1 of 6