DIMENSIONS AND WEIGHTS (NOMINAL) (measured in mm unless noted) Model no. Valve size Insert size L H1 H2 Weight (kgs.) Kv (m 3 /hr) F380.x.E.x.x 15 89.0 61.0 74.0 0.5 5 F380.x.F.x.x 20 20 96.5 63.5 76.2 0.5 7 F380.x.H.x.x 25 105.0 66.0 86.4 0.5 10 F381.x.H.x.x 25 150.0 86.4 94.0 1.5 20 F381.x.J.x.x 32 40 155.0 89.0 107.0 1.5 30 F381.x.K.x.x 40 155.0 89.0 107.0 1.5 30 L H1 H2 MODEL NUMBER SELECTION 1 Insert body size: 380 = 15/20/25mm for 20 mm insert 381 = 25/32/40mm for 40 mm insert Insert kPaD control range: 0 = none 1 = 10-95 kPaD 2 = 22-210 kPaD 4 = 40-390 kPaD 8 = 90-880 kPaD Insert type of end connection: E = 15 mm F = 20 mm H = 25 mm J = 32 mm K = 40 mm Insert p/t plugs requirements: B = pressure/temperature plugs P = taps plugged O = taps open Insert type of thread: = Leave it blank if end connection type is NPT I = ISO Insert valve body material: = Leave it blank for standard body material D = DZR brass Insert valve insert as per selection chart: Insert valve insert as per selection chart: Leave it blank if no insert required F . . . . . . Example: F381.4.K.B.I.F361444 = FlowCon K 40mm ISO female threaded body, standard brass, with p/t plugs and a F361444 insert (1.85 l/sec, 40-390 kPaD). Note 1: Part number and flow rate of insert are indicated on label affixed to body. Tech note · FlowCon K 15-40 mm · may 2023 · www.flowcon.com Page 2 of 6