SPECIFICATIONS (.continued) Pressure sensors (P1 and P2): Supply voltage: Cable: Output: Media temperature: Pressure range 3 : Housing material: Protection: CE conformity: Connection: 12V DC No cable, but with quick-connector 4-20mA -10°C to +85°C / 14°F to +185°F 0-25 bar / 0-360 psi 304 stainless steel IP65 Yes 1/4” ISO Performance data: - Accuracy: - Stability: - Thermal effect on zero: - Thermal effect on span: - Electronic proof: - Response time: Note 3: Calibrated at factory at 24V DC ±1.5% FS (Full Scale) (tolerances can be software compensated in the FlowCon Intelligent Interface) 0.5% FS (Full Scale) ±0.05% ±0.1% FS (Full Scale) ±0.05% FS (Full Scale) Short circuit protection <20 msec (20 sec mean value calculated in the FlowCon Intelligent Interface) DIMENSIONS AND WEIGHT (NOMINAL) Model no. Valve size mm (in) 15 (1/2) L1 mm (in) PICV Valve L2 mm (in) H1 mm (in) H2 mm (in) End connections C 4 ISO Female ISO Male mm (in) mm (in) Sweat mm 22 (0.87) 24 (0.95) 20 FIT.1 20 (3/4) 108 (4.25) 338 (13.3) 185 (7.28) 59 (2.32) 22 (0.87) 25 (0.99) 20 25 (1) - 39 (1.54) 22 25 (1) 35 (1.38) 40 (1.57) 34 FIT.2 32 (1 1/4) 149 (5.87) 338 (13.3) 235 (9.25) 63 (2.48) 33 (1.30) 40 (1.57) 34 40 (1 1/2) 33 (1.30) 42 (1.65) - Note 4: Add end connection length to body length. Note 5: Weight includes PICV valve, PICV actuator (non failsafe), Intelligent Interface and sensor kit, but no end connections. Weight 5 kg (lb) 3.58 (7.89) 5.28 (11.6) BMS L1 C L2 FlowCon FIT.1 Tech note · FlowCon FIT DN15-40 / 1/2”-1 1/2” · september 2023 · www.flowcon.com H1 H2 Page 4 of 11
Download PDF file