SPECIFICATIONS BACnet (SM.0.0.0.6) Protocol: Interface: Device profile: Baud rates supported: Services (BIBBS) supported: BACnet fallback action: Participants: Load: BACnet MS/TP EIA-485 / RS-485 BACnet Application Specific Controller (B-ASC) type server 9600, 19200, 38400, 76800 and 115200 DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B and DM-DCC-B Yes Up to 32 recommended, max. 127 participants 1/8 FlowCon Intelligent Interface Supply voltage: Power consumption: Control signal: Output: Humidity rating: Protection: CE conformity: Cable, 3 groups: • Group 1: • Group 2: • Group 3: Material: • Cover, top: • Cover, bottom: • Bracket: Protocol: Interface: Device profile: Baud rates supported: Services (BIBBS) supported: Participants: Load: 24V AC/DC 4W 2-10V DC 2-10V DC 5.95% rH, no condensation IP54 including upside-down mounting Yes fixed, 1 wire with quick-connector, 3 meter / 9 ft (T1) fixed, 1 wire with quick-connector, 1 meter / 3 ft (T2) fixed, 3 wires 0.6 meter / 2 ft (analog actuator communication) fixed, 2 wires 0.6 meter / 2 ft (power and ground) fixed, 3 wires 0.6 meter / 2 ft (BACnet BMS Communication) fixed, 1 wire with quick-connector, 1 meter / 3 ft (P1) fixed, 1 wire with quick-connector, 1 meter / 3 ft (P2) fixed, 3 wires, 0.6 meter / 2 ft (BACnet actuator communication) PA (glass-reinforced), UL94, V0 rated PC (glass-reinforced), UL94, V0 ratedt St 37-2, powder coated BACnet MS/TP EIA-485 / RS-485 BACnet Application Specific Controller (B-ASC) type server 9600, 19200, 38400,57600, 76800 and 115200 DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DS-RPM-B and DM-RD-B Up to 32 recommended, max. 127 participants 1/8 Tech note · FlowCon FIT DN15-40 / 1/2”-1 1/2” · november 2025 · www.flowcon.com Page 5 of 14
Download PDF file
Table of contents