FlowCon Energy FIT System Energy-Saving Pressure Independent Temperature Control System DN15-40 / 1/2”-1 1/2” SPECIFICATIONS FlowCon PICV valve: Static pressure: Ambient temperature: Media temperature: Material: - Housing and covers: - Stem seals: - Union end connections: - Metal components (internal): - Stem seal and O-rings: - Diaphragm: Stroke: Maximum close off pressure: Maximum operational Δ P: Control characteristic: Control range: Rangeability: Turn down ratio: Shut-off leakage: Flow rate range: End connection 1 : Body taps: Note 1: NPT only available ex. US-factory 2500 kPa / 360 psi -10°C to +50°C / +14°F to +122°F -20°C to +120°C / -4°F to +248°F Forged brass ASTM CuZn40Pb2 EPDM Brass alloy Stainless steel EPDM Hydrogenated acrylonitrile-butadiene-rubber 2160° 600 kPa / 87 psi 320 kPaD / 46 psid Linear flow 1:800 / IEC 60534 >100:1 228:1 ANSI / FCI 70-2 2006 / IEC 60534-4 - Class IV 0.176-2.34 l/sec / 2.78-37.1 GPM Union end connections ISO or NPT 1/4” ISO Tech note · september 2023 · www.flowcon.com Page 1 of 11