FlowCon Energy FIT System Energy-Saving Pressure Independent Temperature Control System DN50-250 / 2”-10” SPECIFICATIONS FlowCon PICV valve: Static pressure: Ambient temperature: Media temperature: Material: - Housing and covers: - Metal components (internal): - Stem seal and O-rings: - Diaphragm: Stroke: Maximum close off pressure: Maximum operational Δ P: Maximum allowable operating pressure: Control characteristic: Control range: Rangeability: Turn down ratio: Shut-off leakage: Flow rate range: End connection: Housing taps: 4000 kPa / 580 psi -10°C to +50°C / +14°F to +122°F -20°C to +120°C / -4°F to +248°F Ductile iron ASTM A395 Grade 60-40-18 Stainless steel EPDM Hydrogenated acrylonitrile-butadiene-rubber 2160° (FIT6: 3600°) 800 kPa / 116 psi 800 kPaD / 116 psid 1600 kPaD / 232 psid Linear flow 1:800 / IEC 60534 >100:1 228:1 ANSI / FCI 70-2 2006 / IEC 60534-4 - Class IV 1.48-76.8 l/sec / 23.4-1220 GPM Universal flange connections which can be used with both ISO and ANSI flanges. Mounting kits are not supplied by FlowCon 1/4” ISO Tech note · april 2024 · www.flowcon.com Page 1 of 13