FlowCon EV Actuators FlowCon Thermal Actuators, NC SPECIFICATIONS FlowCon EV.0.2 Supply voltage: Type: Power consumption: Inrush current: Control signal: Resistance of control voltage input, R E : Failsafe function: End switch: Operation time: Actuating force: Stroke: Ambient temperature: Protection: Cable: 24V AC -10%/+20%, 50/60 Hz Thermal 1 W 320mA (peak) for max 2 min. Analog 0-10V DC 100 kΩ Yes, normally closed 1 No Approximately 2.5 minutes 100N ±5% 5 mm / 0.2 in 0°C to +60°C / +32°F to +140°F IP54 including upside-down, protection class III Plug-in, 3 wires x 0.22 mm 2 , 1 m PVC Plug-in, 3 wires x AWG24, 3.3 ft PVC Note 1: To ensure that the valve is in an open position during commissioning of the system, the actuator will be delivered in open position and remain in this position until it is electrically operated first time. Tech note · august 2024 · www.flowcon.com Page 1 of 5