FlowCon EV Actuators FlowCon Thermal Actuators, NC SPECIFICATIONS FlowCon EV.0.2 Supply voltage: Type: Power consumption: Control signal: Failsafe function: End switch: Operation time: Actuating force: Ambient temperature: Protection: Cable: 24V AC -10%/+20%, 50/60 Hz Thermal 1 W Analog 0-10V DC Yes, normally closed 1 No Approximately 2.5 minutes 100N ±5% 0°C to +60°C / +32°F to +140°F IP54 including upside-down, protection class III Plug-in, 3 wires x 0.22 mm 2 PVC, standard 1 m Plug-in, 3 wires x AWG24 PVC, standard 3.3 ft FlowCon EV.0.3 Supply voltage: Type: Power consumption: Control signal: Failsafe function: End switch: Operation time: Actuating force: Ambient temperature: Protection: Cable: 230V AC ±10%, 50/60 Hz Thermal 1 W ON/OFF Yes, normally closed 1 No Approximately 4 minutes 100N ±5% 0°C to +60°C / +32°F to +140°F IP54 including upside-down, class II Fixed, 2 wires x 0.75 mm 2 PVC, standard 1 m Fixed, 2 wires x AWG18 PVC, standard 3.3 ft Note 1: To ensure that the valve is in an open position during commissioning of the system, the actuator will be delivered in open position and remain in this position until it is electrically operated first time. Tech note · may 2022 · www.flowcon.com Page 1 of 4