FlowCon SM Weather Box 1A95120 - 02/2023 Wiring If feedback signal is not required, leave green wire detached. Remember to remove the protection film from the actuator display to avoid condensation. FlowCon SM (analog) SM.0.0.0.3/4/6 Actuator 0(2)-10V modulating SM.0.0.0.6 Actuator RS-485 Serial BACnet Black Blue White Green Black Red White Input signal 0(2)-10V DC Feedback signal 0(2)-10V DC Power 24V AC/DC Ground/common FlowCon SM (digital) SM.0.0.0.3/4/6 Actuator 2-position, Normally Closed A+ B- Signal ground SM.0.0.0.3/4/6 Actuator 2-position, Normally Open Black Blue White Red Green Black Blue White Red Green Close Open Feedback signal Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 3-point floating, Normally Closed Stop Open Close Feedback signal Power 24V AC/DC Ground/common Black Blue White Red Green Open Close Feedback signal Power 24V AC/DC Ground/common SM.0.0.0.3/4/6 Actuator 3-point floating, Normally Open Stop Close Open Feedback signal Power 24V AC/DC Ground/common Black Blue White Red Green For Start-Up , Programming , Alarms , Auto Stroke , Manual Override and Fail- safe operation , please see FlowCon SM instruction . Direct actuator arrow key actions can easily be done when weather box lid is re- moved. Please use a Phillips head screwdriver to loosen the 4 screws and open the lid for easy access. DO NOT REMOVE ACTUATOR COVER. Opening actuator cover will void warranty. FlowCon International assumes no responsibility for mistakes, if any, in any printed material. This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 2 of 2