Page number 4
FlowCon T Actuators 01/2025 Re-calibration (T.0.2) To initiate a re-calibration process (which can only be done manually), press and release the push button on the PCB while the unit is in normal operation mode. The LED will remain lit, while the actua- tor travels to each end position. The LED will turn off when the process is complete and proceed to normal operation mode (according to control signal) with LED blinking slowly. If the stroke adjustment is set to less than 30°, an alarm will occur (LED will blink 2 times). DIP Switch Settings The valve functions are set on DIP switches found under the actuator cover. Factory setting for all switches is OFF. FlowCon T.0.2 Actuator DIP switch Function ON Factory setting Function OFF #1 % Normally Open % , CCW 90-0° % % Normally Close, CW 0-90° #2 No function No function #3 mA Control signal 4-20mA #4 30 m s A ec Feedback 9 s 0 ign se a c l 4-20mA 1234 30 sec V 90 s V ec Control signal 2-10V Feedback signal 0-10V FlowCon T.0.3 / T.0.4 Actuator DIP switch Function ON #1 % Normally Open % , CCW 90-0° #2 No function Factory setting % 12 Function OFF % Normally Close, CW 0-90° No function LED Status The LED indication is only visible when the actuator cover is removed. The LED indication will give the following statuses. Normal operation mode Calibration mode (closing point adjustment) Power failure alarm Calibration alarm Overtorque alarm Perpetual failure alarm T.0.2 Slow blinking green Full on green 1 red blink 2 red blink 3 red blink 4 red blink T.0.3 Slow blinking green n/a n/a n/a n/a n/a T.0.4 Slow blinking green n/a n/a n/a n/a n/a FlowCon International assumes no responsibility for mistakes, if any, in any printed material. This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 4 of 4