FlowCon SM with BACnet actuator 1B95082 - 02/2023 Choose control mode in MSV.46 (programming menu step 11). Options: 1 = Linear flow 2 = Equal % 3 = Linear rotation 4 = Linear signal Choose whether or not to enable flush at startup in BV.53 (programming menu step 4). Flush enabled, results in the actuator opening the valve almost fully if no control signal is regi- stered at start-up. This function is only available if control signal type is V or mA. Options: 0 = disable 1 = enable Choose whether or not to enable password pro- tection of the actuator in BV.54 (programming menu step 12). If password protection is enabled, the actuator requires a password to enter the programming menu via the buttons on the actuator. Options: 0 = disable 1 = enable Choose the direction of the failsafe action in BV.18 (programming menu step 13). Options: 0 = open 1 = close Condition of the actuator through BACnet Besides checking the values of the objects al- ready described, the following information is available through BACnet: Check the current flow rate (not measured) in AV.68. To know whether the valve is fully closed, please check the motor position in AV.98, if AV.98=0% the valve is fully closed. Check the appropriate pressure in MSV.44.Values: 1 = NA 2 = 32-320kPaD 3 = 40-320kPaD 4/5/7/10 = 30-800kPaD 6 = 50-800kPaD 8/9/11/12 = 35-800kPaD range Check the actuator state in MSV.45. Values: 1 = normal operation 2 = calibration mode 3 = flush mode 4 = auto-stroke 5 = alarm (at least one alarm has been activated) 6 = failsafe (failsafe action has begun) If MSV.45=5, please check for any alarms in BV.55 - BV.62. Values: 0 = no alarm 1 = alarm activated Please note, that the settings and values can not be altered through BACnet while the alarm menu or the programming menu is entered on the actuator. If MSV.40=1 or MSV.40=2, check the control signal value in AV.141. If MSV.40=3, check the control signal in MSV.42. Check unit and value of the feedback signal in AV.164. Check the battery capacity (0-100%) in AV.140. This paper is a supplement to the FlowCon SM Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 3 of 4
Download PDF file