FlowCon SDP 15-25 mm (1/2”-1”) 1H95020 - 04/2019 Installation and Operation Instruction The FlowCon SDP inserts are available with three different FlowCon valve housings, either: FlowCon A DN15/20/25 (1/2”-1”) FlowCon AB DN15/20/25 (1/2”-1”) FlowCon ABV DN15/20/25 (1/2”-1”) Insert Setting and Installation Prior to installing the FlowCon SDP insert (supplied from factory with either fixed 10, 20 or 30 kPaD / 1.45, 2.90 or 4.35 psid), the system should be properly flushed. Blank valve covers are available to be installed during flushing. It is recommended to grease the O-rings located around the insert and headnut with silicone grease before installing the insert in the valve housing. The SDP model is engraved at the top of the insert. Capillary tube Do not damage the capillary tube by compressing or bending the tube with a bending radius below 20 mm (3/4”). Capillary tube is to be finger mounted - DO NOT OVER TIGHTEN. General Assembly Drawing FlowCon SDP A: Valve housing B: SPD insert C: Adjustment key D1: P/t plug (2 pcs.) D2: Plug (2 pcs.) E: Union end connections F: Capillary tube incl. M8 fittings (for QuickDisc®) G: 1/4” to M8 adaptor (for 1/4” body tap) B D1 D2 E A G F E C This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 1 of 2