FlowCon FNP Actuators 1B95070P - 09/2021 LED Status The LED indicator is visible through the dark colored transparent connection cover. The LED indication will give the following statuses. Normal operation mode Calibration mode (closing point adjustment) Electrical override mode FNP Full on green Blinking green Blinking red/green Perpetual failure mode Full on red Re-Calibration Re-calibration can be achieved in one of 2 ways: 1. Forced individual actuator re-calibration can also be performed by flipping DIP switch #6 from OFF to ON and back to OFF on the rele- vant actuator. 2. Forced concurrent re-calibration for all actua- tors is electrically possible. Within 60 sec. provide the following electrical control signal sequence to the grey wire: 10V-2V-10V-2V- 10V-2V to achieve re-calibration. After re-calibration the actuator will go into normal operation mode. This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 3 of 4