Page number 6
FlowCon FIT-G DN40-50 (1 1/2”-2”) 11/2024 Start-up Sequence When power to the actuator is turned on, the actuator will automatically calibrate to determine closing point. Hereafter it will proceed to normal operation mode (according to control signal). For the failsafe version (FH.1), capacitor charg- ing will be prioritized (max. 215 sec depending on capacitor energy level) during start-up and re-powering. After completion of charging mode followed by calibration mode, the actuator will proceed to normal operation mode. Auto Cycle Sequence Auto Cycle can be activated during commission- ing. It prevents the valve from jamming when the valve is not moved for a longer period of inactiv- ity. By moving DIP switch #1 from OFF to ON, Auto Cycle is activated. Actuator will then per- form 50% stroke cycle every 3 weeks if no stroke movement has occurred. Manual Override (FlowCon FH) Before performing manual override, please turn off the power supply. Lift the silicone cap on the top of the actuator to get access to manual over- ride. Manual override is performed by a 4 mm (~5/32”) hex key. Clockwise turning will open the valve and counter-clockwise turning will close the valve. Electrical Override (FlowCon FH.1) By moving DIP switch #6 from OFF to ON, elec- trical override is activated and the actuator will open valve fully. During electrical override the LED indicator will blink red and green. When DIP switch #6 is moved back to OFF, the actuator will re-calibrate and thereafter go into normal opera- tion mode. Electrical override is performed with power supply on. Failsafe Mode (FlowCon FH.1) When power is lost, the actuator will go into fail- safe mode after a few seconds, mandatory that capacitor charging and start-up sequence are completed. The actuator will perform failsafe action (open or close) and stay in failsafe final position until return of power. Upon power, the actuator remains in the final failsafe position until charging mode is reached (max. 215 sec). Here- after the actuator will return to normal operation mode. This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 6 of 8
Page number 7
FlowCon FIT-G DN40-50 (1 1/2”-2”) 11/2024 DIP Switch Settings The valve functions are set on DIP switches found under the connection cover. PCB mounted electri- cal components will not be directly exposed when DIP switches are to be set. Factory setting for all switches is OFF. FlowCon FH Actuator DIP switch Function ON #6 Re-calibration #5 No function % % #4 Equal percentage #3 %% Normally Open %% #2 Control signal 2-10V #1 Auto cycle ON 6 5 4 %% 3 2 1 Function OFF Re-calibration No function % Linear % %% Normally Closed Control signal 0-10V Auto cycle OFF FlowCon FH.1 Actuator DIP switch Function ON #6 Electrical override ON #5 Failsafe open #4 Equal percentage %%% %%% #3 %%% Normally Open %%% #2 Control signal 2-10V #1 Auto cycle ON 6 5 4 %%%%%% 3 2 1 Function OFF Electrical override OFF Failsafe close Linear %%% %%% Normally Closed Control signal 0-10V Auto cycle OFF LED Status The LED indicator is visible through the dark colored transparent connection cover. The LED indication will give the following statuses. Normal operation mode Charging mode (200 sec) Calibration mode (closing point adjustment) Electrical override mode Failsafe mode Perpetual failure mode FH Full on green n/a Blinking green n/a n/a Full on red FH.1 Full on green Blinking red Blinking green Blinking red/green OFF Full on red This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 7 of 8