FlowCon FIT DN15-250 (1/2”-10”) 12/2024 -2 Manual programming of the actuator (SM.0.0.0.3/4/6) The programming menu is always accessible. To enter the program- ming menu, simultaneously press and for 6 seconds, until bottom line in display blinks. To change a value, press or . For quick scroll through values hold down or . Press to accept a value and go to next step and press to go to previous step. For fast menu exit press and simultaneously for 6 seconds. The actuator will automatically return to normal operation mode if no ac- tion is detected on arrow keys for 1 minute. All values selected in the programming menu are stored in non-volatile memory. Step Display Description Values 0 * Enter password. *scrolling top: ENTER PASS WORD Disabled by default Password: 3569266. Only if Enabled (in step 11). Change one digit at a time, press and to move between digits. At last digit, press to go to next step. 1 * Select language. *scrolling top: SELECT LANGUAG Default: English. Possibility to choose other languages later on (not currently an option). 2 * 3 * Select valve model onto which the actuator is installed. *scrolling top: SELECT VALVE MODEL Choose unit scale for flow rate. *scrolling top: SELECT UNIT SCALE Default: SM.0.0. Select from the 11 available valve models, starting from SM.1.1. Options: SM.1.1, SM.2.1, SM. Default: l/sec. Options: l/sec or l/hr or GPM. 4 * 5 * Activate Flush mode at start-up. *scrolling top: SELECT FLUSH MODE Select type of control signal. *scrolling top: SELECT CONTROL SIGNAL Default: Enable. Options: Enable or Disable. When no control signal (analog) is detected at start-up, flush mode is started (5/6 of fully opened). It will be dismissed when control signal is detected. Default: 2-10VDC. Leave at default: 2-10V DC for SM.0.0.0.3/4 Set to: BACnet for SM.0.0.0.6 This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 6 of 12
Page number 7
FlowCon FIT DN15-250 (1/2”-10”) 12/2024 -2 Step Display 6 * Description Select minimum control value. *scrolling top: SET MINIMUM LIMIT Values Volt default: 2. Leave at default: 2. 7 * Select maximum control value. *scrolling top: SET MAXIMUM LIMIT Volt default: 10. Leave at default: 10. 8 * Select feedback signal. *scrolling top: SELECT FEEDBAC SIGNAL Default: AU; Automatic match of control signal. Leave at default: AU 9 * 10 * rotatio NC 11 * 12 * 13 * failsaf close 14 * 15 * Set the designed maximum flow. Accuracy: Greatest of either ±5% of controlled flow or ±2% of max. valve flow. *scrolling top: SELECT MAXIMUM FLOW Select direction of rotation. *scrolling top: SELECT ROTAT DIRECT Select actuator mode. *scrolling top: actuator mode Activate password. *scrolling top: ACTIVAT PASS WORD Select direction of rotation when Failsafe. *scrolling top: SELECT FAIL SAFE DIRECT Select communication speed for PICV actuator. *scrolling top: select baud rate Select MAC address for PICV actuator. *scrolling top: select mac address Default: Maximum setting. Values depend on valve model and unit scale chosen in step 2 and 3. Stepping increments as per tech note. Default: Normally Closed (NC). Leave at default: Normally Closed (NC). Default: Linear flow. Leave at default: Linear flow Default: Disable. Options: Enable or Disable. If Enabled password is required to access alarm and programming menu. Default: Close. Options: Open or Close. Only valid for SM.0.0.0.4/6 (failsafe models). Failsafe direction open means opening to max. flow chosen in step 9. Default: 9600. Leave at default: 9600 Only valid for SM.0.0.0.6 (BACnet model). Default: 000. Leave at default: 000 Only valid for SM.0.0.0.6 (BACnet model). This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 7 of 12