FlowCon Partner Globe DN65-300 (2”-12”) 04/2024 Installation and Operation Instruction The FlowCon Partner Globe is available in 8 different flanged sizes: • FlowCon Partner Globe DN65-300 (2”-12”). Figure 1 Installation Prior to installing the FlowCon Partner Globe (supplied from factory in setting 0.0 due to cali- bration), the system should be properly flushed. Remember to remove dust caps if valves are provided with such. Setting After installation, setting is done by turning the hand wheel (turned from setting 0.0 and up) - no tools required. Scale setting is located on top of the hand wheel where the outer digits , numbered 1 to 8 (DN65-150 / 2 1/2”-6”) or 1 to 11 (DN200-300 / 8”-12”), indicate full turns and the inner digit , numbered 0 to 9, indicates 1/10 of Allen key full turn. Clockwise turning will reduce flow and counter-clockwise turning will increase flow. Capillary tube Capillary tube is as standard supplied with the DPCV valve along with required 1/4” NPT to 1/4” ISO adaptor. Do not damage the capillary tube by compressing or bending the tube with a bending radius below 20 mm (3/4”). Capillary tube is to be finger mounted in the outlet body tapping of the FlowCon Partner Globe instead of the supplied p/t plug and tightened with 1-3Nm - DO NOT OVER TIGHTEN. Locking 1. Remove the top wheel cap with e.g. a flat screwdriver. 2. Close the valve completely by turning the hand wheel clockwise till fully closed. Check the scale to be 0.0. 3. Open to required position by turning counter- clockwise. 4. Turn clockwise and fully tighten the lock screw with a 5 mm (1/5”) Allen key, valve setting is now locked to current setting. 5. Return the wheel cap and click it in place. Figure 2 This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 1 of 6
Download PDF file