FLOW RATE TABLES FlowCon Pure DN40 (1 1/2”) valve · 90-880 kPaD (13-128 psid) Flow # Flow (l/sec) 11 0.069 01 0.095 02 0.126 03 0.189 04 0.252 05 0.315 06 0.379 07 0.442 08 0.505 10 0.631 12 0.757 14 0.883 16 1.01 Accuracy: ±10% of controlled flow rate. Flow (l/hr) 250 340 454 681 909 1140 1360 1590 1820 2270 2730 3180 3630 Flow (GPM) 1.1 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0 12.0 14.0 16.0 FlowCon Pure DN50 (2”) valve · 90-880 kPaD (13-128 psid) Flow # Flow (l/sec) 09 0.568 10 0.631 12 0.757 14 0.883 16 1.01 18 1.14 20 1.26 22 1.39 24 1.51 26 1.64 28 1.77 30 1.89 32 2.02 34 2.15 36 2.27 38 2.40 40 2.52 42 2.65 44 2.78 Accuracy: ±10% of controlled flow rate. Flow (l/hr) 2040 2270 2730 3180 3630 4090 4540 4500 5450 5910 6360 6810 7270 7720 8180 8630 9090 9540 9990 Flow (GPM) 9.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0 32.0 34.0 36.0 38.0 40.0 42.0 44.0 Tech note · FlowCon Pure 316 SS · may 2021 · www.flowcon.com Page 3 of 4