SPECIFICATIONS (.continued) FlowCon Actuators: FlowCon Actuator 2 Supply voltage Power consumption Control signal Operation time Ambient temperature Protection Cable Weight Including end switch Switching point EV.0.2 24V AC -10%/+20% 50/60Hz 1.0 watt 0-10V DC normally closed 3 Approx. 2½ min 0ºC to +60ºC IP54, class III Plug-in, 1 meter 0.127 kg 4 No N/A EV.0.3 230V AC ±10% 50/60Hz 1.0 watt ON/OFF normally closed 3 Approx. 4 min 0ºC to +60ºC IP54, class II Fixed, 1 meter 0.116 kg 4 No N/A EV.0.4 24V AC/DC -10%/+20% 50/60Hz 1.0 watt ON/OFF normally closed 3 Approx. 4 min 0ºC to +60ºC IP54, class III Fixed, 1 meter 0.116 kg 4 No N/A EV.0.5 120V AC ±10% 50/60Hz 1.0 watt ON/OFF normally closed 3 Approx. 4 min 0ºC to +60ºC IP54, class II Fixed, 1 meter 0.116 kg 4 No N/A EV.1.3 230V AC ±10% 50/60Hz 1.0 watt ON/OFF normally closed 3 Approx. 4 min 0ºC to +60ºC IP54, class II Fixed, 1 meter 0.166 kg 4 Yes Approx. 2mm Switching capacity N/A 230V AC N/A N/A N/A 5A ohm resistive load 1A inductive load Note 2: FlowCon warranty is voided using other actuators than supplied or recommended by FlowCon International. Note 3: To ensure that the valve is in an open position during commission of the system, the actuator will be delivered in a normal open position and remain in this position until it is electrically operated first time. Note 4: The weight includes actuator, adaptor ring and 1 meter cable. EV.1.4 24V AC/DC -10%/+20% 50/60Hz 1.0 watt ON/OFF normally closed 3 Approx. 4 min 0ºC to +60ºC IP54 Fixed, 1 meter 0.166 kg 4 Yes Approx. 2mm 24V AC 3A ohm resistive load 1A inductive load FlowCon EV.0.2, EV.1.3 and EV.1.4 Valve adaptor, grey FlowCon EV.0.3, EV.0.4 and EV.0.5 Valve adaptor, grey Tech note · FlowCon EVC · september 2023 · www.flowcon.com Page 2 of 10
Download PDF file