GENERAL DESCRIPTION The FlowCon DPCV series are differential pressure control valves. Each valve has an adjustable differential pressure setting to enable differential pressure limitation for balancing or avoiding noise from the sub system that the valve is controlling. Furthermore, the DPCV can be used as a shut-off valve. The FlowCon DPCV is easy to adjust without special equipment or conversion tables since the setting is printed directly on the valve which is adjusted by hand. The valve is tamper-proof when the supplied lock ring is fastened with a cable binder. DIFFERENTIAL PRESSURE LIMITATION SETTINGS General settings of ΔPcontrolled Min. kPaD 25 30 35 40 45 50 55 psid 3.6 4.4 5.1 5.8 6.5 7.3 8.0 Operational ΔP Max./Recommended max. kPaD 210/90 210/110 210/130 210/150 210/170 210/190 210/210 psid 30/13 30/16 30/19 30/22 30/25 30/28 30/30 Setting 5 10 15 20 25 30 35 kPaD 5 10 15 20 25 30 35 psid 0.7 1.5 2.2 2.9 3.6 4.4 5.1 Accuracy: Greatest of either ±25% of controlled differential pressure or ±10% of maximum differential pressure. Turn the top wheel by hand until the setting is reached. The picture shows a setting of 5 kPa (factory setting). For a more precise setting or to reach a setting in between the settings in the table, please measure the controlled differential pressure while adjusting the setting. Tech note · FlowCon DPCV 15-50mm · february 2016 · www.flowcon.com Page 3 of 5