FlowCon Pure 40-50 mm (1 1/2”-2”) 1B95100 - 05/2021 Installation and Operation Instruction The FlowCon Pure valve is available with This automatic balancing vavle is a built-in pre- clamp ferrules for TriClover connection accord - set flow-limiter. Select part number from below ing to ISO 2852. flow tables. Flow # 11 01 02 03 04 05 06 07 08 10 12 14 16 FlowCon Pure DN40 (1 1/2”) valve · 90-880 kPaD (13-128 psid) Flow (l/sec) Flow (l/hr) 0.069 250 0.095 340 0.126 454 0.189 681 0.252 909 0.315 1140 0.379 1360 0.442 1590 0.505 1820 0.631 2270 0.757 2730 0.883 3180 1.01 3630 Flow (GPM) 1.1 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0 12.0 14.0 16.0 Flow # 09 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 FlowCon Pure DN50 (2”) valve · 90-880 kPaD (13-128 psid) Flow (l/sec) Flow (l/hr) 0.568 2040 0.631 2270 0.757 2730 0.883 3180 1.01 3630 1.14 4090 1.26 4540 1.39 4500 1.51 5450 1.64 5910 1.77 6360 1.89 6810 2.02 7270 2.15 7720 2.27 8180 2.40 8630 2.52 9090 2.65 9540 2.78 9990 Accuracy: ± 10% of controlled flow rate. Flow (GPM) 9.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0 30.0 32.0 34.0 36.0 38.0 40.0 42.0 44.0 This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www.flowcon.com Page 1 of 2